Contact us NOWCONTACT US NOW

Self Limiting Heating Cable - W-Class Cable

W-Class Cable for Temperature Maintenance, for Domestic Hot Water, Warm Water Pipe, Oily Wastewater and Medium Temperature Maintenance.

Self Regulating Heating Cable

 

 

 

Download Free Datasheet

SRCable-W.pdf

W-Class-Cable -Warm Water

For Temperature Maintenance, for Domestic Hot Water,  Warm Water Pipe, oily Wastewater, Tank, Valves, also to avoid the Risk of Legionella, ,..

By using our heat tracer you get the best heat tracing system. They are designed to maintain networks of warm water temperature and avoid the risk of legionella.
Self Limiting or Self Regulating Technology allows easy operation safely. The power changes depending on the temperature and prevents overheating. When it is cold, the polymer shrinks and facilitates the flow of current, thereby increasing the temperature of the cable. As it gets warmer, the polymer expands and prevents the current: the Self Regulating cable heats less than before.
Finally, a « parallel » technology allows the cable to be cut to desired length directly on the site. Exact fit the length of heating cable for your needs.
The CableBox storage system on coil allows easy handling, quick and convenient. This product is in stock and can be used with the fast connector system DomoClick®

WORLDTRACE-W Trace Heating cables applications

  • Frost protection for heating lines
  • Tanks and Vessels
  • Food processing industry
  • Heat tracing on fat lines
  • Drainage lines in canteens and large-scale kitchens
  • Avoid Legionella formation
  • Pipe heat tracing

Self Regulating WORLDTRACE W-Cable advantages

  • Self-Regulating Heating Cable
  • Can be cut to length on site
  • Moisture proof

WORLDTRACE-W Self Regulating Heating Cable Description

  1. Bus wire Cu nickel-plated (2x1.23mm²) 
  2. Self limiting heating element
  3. Insultation
  4. Tin-plated copper protective earth wires with Protective aluminium foil
  5. Thermoplastique outer jacket

WORLDTRACE W-Cable Datasheet

Nominal Voltage 230V

Maximum length circuit:

  • W-55………… 130 m
  • W-65………… 110 m

Minimum Bending Radius 27 mm                           

Weight approx. 90 kg/km (alufoil)

Minimum installation temperature -20°C                

Maximum exposure temperature (energised) 80°C

Maximum exposure temperature (deenergised) 100°C               

Power Curve